Welcome to Guangdong Yuebiao Electric Co., Ltd.
1.LOTO: Disconnect, verify zero voltage, and ground
2.Remove: Open covers, loosen torque bolts, lift out old section
3.Install: Align new section, connect joints, torque to spec, secure clamps
4.Test: Insulation ≥20 MΩ, no-load 30min, gradually load to 100%
Procedure follows industry maintenance standards to ensure uptime in mission-critical data halls.
M8: 22–30 N·m
M10: 45–59 N·m
Shear-head design ensures correct torque without a torque wrench. If cap does not shear, disassemble and clean threads. Supports reliable field performance in industrial corridors.
Support spacing: 1.5–2m, aligned using laser level
Two-person lift, avoid dragging
Torque shear-head bolts until cap snaps: M8 22–30 N·m, M10 45–59 N·m
Final: 500V insulation test per industry standards
Ensures stability before energization in commercial towers
Front: LV 0.6m, MV 0.9m per international installation standards
Top: 0.3m
Side: 0.2m
IR scanning: recommend 1.0m front clearance.
Data halls require optimized shaft widths for regular thermal inspection.
Seal gaps using intumescent putty, boards, or wraps per building fire codes.
Compact type: external wrap
Air-insulated type: internal barrier + external seal
UL-listed fire-block kits can be installed in 10 minutes, stabilizing fire compartments in commercial towers.
Five mandatory checks per internal commissioning procedures:
1.Visual: deformation, damage, corrosion
2.Torque: M8 22–30 N·m, M10 45–59 N·m
3.Grounding: PE continuity <0.1Ω
4.Phase ID: colors match single-line diagram
5.Insulation resistance: ≥20 MΩ @ 500/1000V
Ensures system stability before first energization in critical facilities.
UL 857: North American standard for utility interconnections.
IEC 61439-6: International standard for commercial and industrial busway systems.
Selection depends on region: US projects require UL, Asia/Europe/Middle East use IEC. Same copper stock can be dual-labeled; differences are only in certification marking.
ISO 9001, CQC Certification.
Compliance: dielectric strength, temperature-rise ≤70K, mechanical integrity verified per industry standards. Globally recognized for commercial towers and industrial export projects.
Tests include impedance, IP rating, and temperature-rise verification. Sample value can be credited against first bulk order within 60 days.
Standard: 30% deposit, progress payments, balance before shipment. Large projects: milestone structure (30%/40%/30%) linked to raw material, assembly, testing. Letter of credit accepted for first-time international clients.
Fully customizable: straight sections, elbows, reducers, fire barriers, and double-deck stacks. Supports complex data hall layouts and architectural curves.
Provide four key documents for a 24-hour turnaround:
1、Single-line diagram (ampacity, voltage, short-circuit kA)
2、Floor plan (routing and obstacles)
3、Riser diagram (floor heights)
4、Transformer short-circuit rating
Essential for accurate cost estimation and system stability.